3 Phase Power Analyzer
Description:
Power and harmonics analyzer.
Features:
- True RMS value (V and A)
- Leakage Current Measurement at 10 μ A Resolution
- HARMONIC Analysis (V and A) to the 99th Order
- Better Understanding of High Frequency Harmonic Analysis (up to 5/6 KHz)
- Non-interrupted Harmonic Analysis
- Analysis of Total Harmonic Distortion (THD-F)
- Analysis of Crest Factor (C.F.)
General Specification | |
Conductor Size | 30mm (approx.) |
Battery Type | 1.5V SUM-3 x 2 |
Display | 4+2+2 digits LCD |
Power Consumption | 5mA (approx.) |
Auto-Power-Off | 30 minutes |
No. Of Samples/Period | 512 (V & A), 256 (W) |
LCD update rate | 2 times / sec. |
Weight | 200g (battery included) |
Operating Temperature | -10 ° C to 50° C |
Operating Humidity | < 85% relative |
Storage Temperature | -20° C to 60° C |
Storage Humidity | < 75% relative |
Dimension | 210 (L) x 62 (W) x 35.6mm (H), 8.3" (L) x 2.5" (W) x 1.4" (H) |
Accessories | test leads, Carrying bag x 1, Users manual x 1, Batteries 1.5V x 2 |
Option | alligator clips |
AC Current (50 or 60 Hz, True RMS)
Range(Model 19,21) | Range(Model 23) | Resolution | Accuracy of Readings |
0.30 – 60.00mA | 0.30 – 60.00mA | 0.01mA | ±0.5% ± 5dgts |
60.0 – 600.0mA | 60.0 – 600.0mA | 0.1mA | ±0.5% ± 5dgts |
0.030 – 3.000 A | 0.030 – 9.999 A | 0.001 A | ±0.5% ± 5dgts |
3.00 – 30.00 A | 10.00 – 60.00 A | 0.01 A | ±0.5% ± 5dgts |
30.00 – 50.00 A | 6 0.00 – 99.99 A | 0.01 A | ±1.0% ± 5dgts |
AC Voltage (50 or 60 Hz, True RMS)
Range | Resolution | Accuracy of R. | Range | Resolution | Accuracy of R. |
3V – 250V | 0.1 V | ±0.5% ± 5dgts | 250V – 600V | 0.1 V | ±0.5% ± 5dgts |
Harmonics of AC Voltage in % and Magnitude (1 to 99th order)
Range | Resolution | Accuracy in % | Resolution | Accuracy in Magnitude |
50V – 600V | 0.1 % | ±0.5% | 0.1 V | ±0.5% ± 0.5V |
Harmonics of ACA in % Percentage and Magnitude (1 to 99th order)
Range(Model 19, 21) | Range(Model 23) | Res. | Accuracy (%) | Res. | Accuracy of R. |
10.00 – 60.00mA | 10.00 – 60.00mA | 0.1 % | ±0.5% | 0.01mA | ±0.5% ± 0.1mA |
60.0 – 600.0mA | 60.0 – 600.0mA | 0.1 % | ±0.5% | 0.1mA | ±0.5% ± 1mA |
0.5 – 3.000 A | 0.5 – 9.999 A | 0.1 % | ±0.5% | 0.001 A | ±0.5% ± 0.01 A |
3.00 – 30.00 A | 10.00 – 60.00 A | 0.1 % | ±0.5% | 0.01 A | ±0.5% ± 0.1 A |
30.00 – 60.00 A | 6 0.00 – 99.99 A | 0.1 % | ±1.0% | 0.01 A | ±1.0% ± 0.1 A |
Power Factor and Phase Angle (PF, Φ ,Model 21 and 23)
Range(PF) | Resolution | Accuracy | Range(Φ) | Resolution | Accuracy |
0.000 – 1.000 | 0.001 | ± 1° | -180° to 180° (0 ° to 360 ° ) | 0.1° | ± 1° |
Total Harmonic Distortion (THD-F, 1 to 99th order) Crest Factor (C.F., Accuracy of Readings)
Range | Resolution | Accuracy ofR. | Range | Resolution | Accuracy ofR. |
0.0–999.9% | 0.1% | ± 0.5% ± 5 digits | 1.00 – 99.99 | 0.01 | ± 5% ± 30 digits |