3 Phase Power Analyzer
Description:
Power harmonics analyzer.
Features:
- Analysis for 3P4W, 3P3W, 1P2W, 1P3W
- True RMS Value (V 123 and L123)
- Active Power (W, KW, MW, GW)
- Apparent and Reactive Power (KVA, KVAR)
- Power Factor (PF), Phase Angle (Φ)
- Energy (WH, KWH, KVARH, PFH)
- Current Measurement from 0.1mA to 3000A, Capable of Analyzing IT Standby Power Consumption to the Maximum Demand of a Factory
- Display of 35 Parameters in One Screen(3P4W)
- Programmable CT (1 to 600) and PT (1 to 3000) Ratios
- Display of Overlapped Voltage and Current Waveform
- 2.4M Memory with Programmable Interval (1 to 6000 seconds, 17000 Records for 3P4W System)
- Output of Waveform, Power Parameters and Harmonics at Command
- Large Dot Matrix LCD Display with Backlight
- Average Demand (AD in W, KW, MW)
- Maximum Demand (MD in W, KW, MW) with Programmable Period
- Harmonic Analysis to the 99th Order
- Display of 50 Harmonics in One Screen with Waveform
- Display of Waveform with Peak Values (1024 Samples/Period)
- Analysis of Total Harmonic Distortion (%THD-F)
- Graphic Phasor Diagram with 3 Phase System Parameters
- Capture 28 Transient Events (Time + Cycles) with Programmable Threshold(%)
- 3 Phase Voltage Unbalance Ratio (VUR)
- 3 Phase Voltage Unbalance Factor (d0%, d2%)
- Calculated Unbalance Current through Neutral Line (In)
- Optical isolated USB Interface
- Built-in Timer and Calendar for Data Logging
- Conductor Size: -Model 6801 30mm(approx) -Model 6802 5
- 55mm(approx),64*24mm(bus bar) -Model 3007 170mm(approx)
Technical Specification:
AC Watt (50 or 60 Hz, PF 0.5 to 1, CT=1)
Range | Resolution | Accuracy of Readings | ||
6800+6801 | 8800+6802 | 6800+3007 | ||
5.0 - 999.9 W | 0.1 W | ±1% ± 8dgts | ±1% ± 8dgts | ±1% of VA Range ± 8dgts |
1.0000 - 999.9 KW | 0.001 KW | ±1% ± 8dgts | ±1% ± 8dgts | ±1% of VA Range ± 8dgts |
10.00 - 99.99 W | 0.01 KW | ±1% ± 8dgts | ±1% ± 8dgts | ±1% of VA Range ± 8dgts |
100.0 - 999.9 KW | 1 KW | ±1% ± 8dgts | ±1% ± 8dgts | ±1% of VA Range ± 8dgts |
1000 - 9999 KW | 1 KW | ±1% ± 8dgts | ±1% ± 8dgts | ±1% of VA Range ± 8dgts |
0.000 - 999.9 MW | 0.001 MW | - | ±1% ± 8dgts | ±1% of VA Range ± 8dgts |
AC Current (50 or 60Hz, Auto Range,True RMS,Crest Factor<4,CT=1)
Range | Resolution | Accuracy of Readings | |
6800+6801 (Overload Protection AC200A) | 0.050 - 9.999A | 0.001A | ±0.5% ± 5dgts |
10.00 - 60.00A | 0.01A | ±0.5% ± 5dgts | |
60.00 - A99.99 | 0.01A | ±1.5% ± 5dgts | |
6800+6802 (Overload Protection AC2000A) | 0.04 - 10.00A | 0.01A | - |
0.4A - 100.0A | 0.1A | ±0.5% ± 5dgts | |
4.0 - 1000.0A | 1A | ±0.5% ± 5dgts | |
6800+3007 (Overload Protection AC3500A) | 4 - 300A | 0.1A | ±1% ± 5dgts |
300.0 - 999.9A | 0.1A | ±1% ± 5dgts | |
1000 - 3000A | 1A | ±1% ± 5dgts |
AC voltage (50 or 60 Hz, Auto Range, Truw RMS, Crest Factor<4)
Range | Resolution | Accuracy of Readings | Range | Resolution | Accuracy of Readings |
4.0V - 500.0 (Phase to Neutral) | 0.1V | ± 0.5% ± 5dgts | 4.0 - 600.0V (Phase to phase) | 0.1V | ± 0.5% ± 5dgts |
Harmonics of AC Voltage in % and in Magnitude
(1 to 99th order, minimum voltage at the 50 or 60 Hz >AC 80V)
Range | In Percentage | In Magnitude | ||
Resolution | Accuracy of reading | Resolution | Accuracy of readings | |
1 - 20 th | 0.1% | ± 2% | 0.1V | ±2%±0.5V |
21 - 49th | 4% of reading ±2.0% | 4% of reading ±0.5A | ||
50 - 99 th | 6% of reading ±2.0% | 6% of reading ±0.5A |
Harmonics of AC current in % and in Magnitude
Model 6800+6801 (100A)
(1 to 99 th order, minimum current at 50 or 60 Hz is greater than 10% of the range)
Range | In Percentage | In Magnitude | ||
Resolution | Accuracy of reading | Resolution | Accuracy of readings | |
1 - 10 th | 0.1% | ± 2% of reading ± 1% | 0.1mA/ 0.1A | ± 0.2% of reading ± 7dgts |
11 - 20th | ± 2.0% of reading ± 1% | ± 2% of reading ± 7dgts | ||
21 - 50th (A range) | ± 5% of reading ± 1% | ± 5% of reading ± 7 dgts | ||
21 - 50th (mA range) | ± 10% of reading ± 1% | ± 10% of reading ± 7 dgts | ||
51 - 50th | ± 35% of reading ± 1% | ± 35% of reading ± 7 dgts |
Model 6800+6802(1000A);6800+3007(3000A)(1 to 99th order, minimum current at the 50 or 60 Hz>20A)
Range | In Percentage | In Magnitude | ||
Resolution | Accuracy of reading | Resolution | Accuracy of readings | |
1 - 20th | 0.1% | ± 2% | 0.1A (6802)/ 0.3A(3007) | ± 2% of reading ± 0.4A/0.6A |
21 - 49th | 4% of reading ±2.0% | ± 4% of reading ± 0.4A/0.6A | ||
50 - 99th | 6% of reading ±2.0% | ± 6% of reading ± 0.4A/0.6A |
Total Harmoic Distortion
Range | Resolution | Accuracy (6801) | Accuracy (6802) | Accuracy (3007) |
0.0-20% | 0.1% | ± 1% | ± 2% | ± 2% |
20-100% | 0.1% | ± 3% of reading ± 5% | ± 6% of reading ± 1% | ± 6% of reading ± 1% |
100-999.9% | 0.1% | ± 10% of reading ± 10% | ± 10% of reading ± 1% | ± 10% of reading ± 1% |
Peak Value of Ac Voltage or AC Current, VT=1
Range | Sampling Time | Accuracy of reading |
50Hz | 39μS | ±5% ±30digits |
60Hz | 33μS | ±5% ±30digits |
Crest Factor (C.F.) of ACV or ACA, VT=1
Range | Resolution | Accuracy of reading |
1.00-99.99 | 0.01 | ±5% ±30digits |
Frequency in AUTO mode
Range | Resolution | Accuracy of reading |
45-65 Hz | 0.01 Hz | 0.1 Hz |
Power Factor (PF)
Range | Resolution | Accuracy of reading |
0.00-1.00 | 0.01 | ±0.04 |
Phase Angle (Φ)
Range | Resolution | Accuracy of reading |
-180 to 180 degree | 0.1 degree | ±1 degree |
General Specification | |
Conductor Size | 30mm (approx.) |
Conductior Size | 55mm(approx.), 64 X 24mm(Bus Bar) |
Battery Type | 1.5V SUM-3 x 8 |
Display | Bot Matrix LCD with backlight |
Power consumption | 140mA (approx.) |
External DC Input | DC 12V adaptor (for safety purpose, the adaptor must be certified with 600Visolation protection) |
LCD update rate | 1 times/sec |
No. of samples/period | 1024 |
Operating Humidity | <85% relative |
Operating temperature | -10°C to 50°C |
Storage Humidity | <75% relative |
Weight | 1160g |
Dimension (6800) | 257 (L) x 155 (W) x 57 (H) mm ,10.1"(L) x 6.1" (W) x 2.3" (H) |
Dimension (6801) | 210 (L) x 62 (W) x 36 (H) mm ,8.3 " (L) x 2.5" (W) x 1.4" (H) |
Dimension (6802) | 244 (L) x 97 (W) x 46 (H) mm ,9.6 " (L) x 3.8" (W) x 1.8" (H) |